Procedure :
Fill in the quantities in the windows. The Template will calculate the figure for column #10
Fill in Speaker Watts in Column # 4 and TOTAL Strobe Current in Column # 6.
1
2
3
4
5
6
7
8
9
10
Description
INSERT
Quantity
Standby (A)
INSERT
Total Speaker Loads (Watts)
INSERT
Standby Hours
ALARM Current (A)
INSERT
Alarm Time
Standby Load Columns Used
Alarm Load Columns Used
Extension Ampere Hours
EVAC 101-RMT
0.065
2 * 3 * 5
EVAC 101-RMT in ALARM
0.35
2 * 6 * 7
101-SPK module. Standby
0.01
2 * 3 * 5
101-SPK module in ALARM
0.03
2 * 6 * 7
101-STRB module. Standby
0.01
2 * 3 * 5
101-STRB module in ALARM
0.03
2 * 6 * 7
DMR. Standby
0
2 * 3 * 5
DMR. Alarm
0.065
2 * 6 * 7
RMT-PG Standby
0.015
2 * 3 * 5
RMT-PG ALARM
0.06
2 * 6 * 7
MAX Speaker Load (Watts)
0.05
4 * 6 * 7
Strobe Load
0.75
6 * 7
Column # 8 is the system load on standby with NO alarm
Total = Sum of Column # 10
Column # 9 is the additional load during alarm
Add 15% Safety Margin
Column # 10 is the calculated AH for the row
Total AH
Note # 1: Speaker in Watts is automatically converted to equivalent Load Current.
Note # 2: Strobe Load is the total of strobe current in alarm.